apparent power |
1.8 kVA at 240 V |
continuous output current |
4.6 A at 230 V |
maximum transient current |
5.1 A for 60 s |
speed drive output frequency |
0.5…200 Hz |
speed range |
1…10 |
speed accuracy |
+/- 10 % of nominal slip 0.2 Tn to Tn |
local signalling |
1 LED (red) for DC bus energized |
output voltage |
<= power supply voltage |
isolation |
Electrical between power and control |
type of cable |
Without mounting kit: 1 wire(s)IEC cable at 45 °C, copper 90 °C / XLPE/EPR
Without mounting kit: 1 wire(s)IEC cable at 45 °C, copper 70 °C / PVC
With UL Type 1 kit: 3 wire(s)UL 508 cable at 40 °C, copper 75 °C / PVC |
electrical connection |
VIA, VIB, FM, FLA, FLB, FLC, RY, RC, F, R, RES: terminal 2.5 mm² / AWG 14
L1/R, L2/S, L3/T: terminal 6 mm² / AWG 10 |
tightening torque |
1.3 N.m, 11.5 lb.in (L1/R, L2/S, L3/T)
0.6 N.m (VIA, VIB, FM, FLA, FLB, FLC, RY, RC, F, R, RES) |
supply |
Internal supply for reference potentiometer (1 to 10 kOhm): 10.5 V DC +/- 5 %, <10 A, protection type: overload and short-circuit protection
Internal supply: 24 V DC (21…27 V), <200 A, protection type: overload and short-circuit protection |
sampling duration |
2 ms +/- 0.5 ms F discrete
2 ms +/- 0.5 ms R discrete
2 ms +/- 0.5 ms RES discrete
3.5 ms +/- 0.5 ms VIA analog
22 ms +/- 0.5 ms VIB analog |
response time |
FM 2 ms, tolerance +/- 0.5 ms for analog output(s)
FLA, FLC 7 ms, tolerance +/- 0.5 ms for discrete output(s)
FLB, FLC 7 ms, tolerance +/- 0.5 ms for discrete output(s)
RY, RC 7 ms, tolerance +/- 0.5 ms for discrete output(s) |
accuracy |
+/- 0.6 % (VIA) for a temperature variation 60 °C
+/- 0.6 % (VIB) for a temperature variation 60 °C
+/- 1 % (FM) for a temperature variation 60 °C |
linearity error |
VIA: +/- 0.15 % of maximum value for input
VIB: +/- 0.15 % of maximum value for input
FM: +/- 0.2 % for output |
analogue output type |
FM switch-configurable voltage 0...10 V DC, impedance: 7620 Ohm, resolution 10 bits
FM switch-configurable current 0...20 mA, impedance: 970 Ohm, resolution 10 bits |
discrete output type |
Configurable relay logic: (FLA, FLC) NO - 100000 cycles
Configurable relay logic: (FLB, FLC) NC - 100000 cycles
Configurable relay logic: (RY, RC) NO - 100000 cycles |
minimum switching current |
3 mA at 24 V DC for configurable relay logic |
maximum switching current |
5 A at 250 V AC on resistive load - cos phi = 1 - L/R = 0 ms (FL, R)
5 A at 30 V DC on resistive load - cos phi = 1 - L/R = 0 ms (FL, R)
2 A at 250 V AC on inductive load - cos phi = 0.4 - L/R = 7 ms (FL, R)
2 A at 30 V DC on inductive load - cos phi = 0.4 - L/R = 7 ms (FL, R) |
discrete input type |
F programmable 24 V DC, with level 1 PLC, impedance: 4700 Ohm
R programmable 24 V DC, with level 1 PLC, impedance: 4700 Ohm
RES programmable 24 V DC, with level 1 PLC, impedance: 4700 Ohm |
discrete input logic |
Positive logic (source) (F, R, RES), <= 5 V (state 0), >= 11 V (state 1)
Negative logic (sink) (F, R, RES), >= 16 V (state 0), <= 10 V (state 1) |
dielectric strength |
2830 V DC between earth and power terminals
4230 V DC between control and power terminals |
insulation resistance |
>= 1 mOhm 500 V DC for 1 minute |
frequency resolution |
Display unit: 0.1 Hz
Analog input: 0.024/50 Hz |
communication service |
Read holding registers (03) 2 words maximum
Write multiple registers (16) 2 words maximum
Write single register (06)
Time out setting from 0.1 to 100 s
Monitoring inhibitable
Read device identification (43) |
option card |
Communication card for LonWorks |
power dissipation in W |
63 W |
air flow |
22 m3/h |
specific application |
HVAC |
Variable speed drive application selection |
Building - HVAC Compressor for scroll
Building - HVAC Fan
Building - HVAC Pump |
Motor power range AC-3 |
0.55…1 kW at 200…240 V 3 phases |
motor starter type |
Variable speed drive |
discrete output number |
2 |
analogue input number |
2 |
analogue input type |
VIA switch-configurable voltage: 0...10 V DC 24 V max, impedance: 30000 Ohm, resolution 10 bits
VIB configurable voltage: 0...10 V DC 24 V max, impedance: 30000 Ohm, resolution 10 bits
VIB configurable PTC probe: 0...6 probes, impedance: 1500 Ohm
VIA switch-configurable current: 0...20 mA, impedance: 250 Ohm, resolution 10 bits |
analogue output number |
1 |
physical interface |
2-wire RS 485 |
connector type |
1 RJ45
1 open style |
transmission rate |
9600 bps or 19200 bps |
transmission frame |
RTU |
number of addresses |
1…247 |
data format |
8 bits, 1 stop, odd even or no configurable parity |
type of polarization |
No impedance |
asynchronous motor control profile |
Voltage/frequency ratio, 2 points
Voltage/frequency ratio - Energy Saving, quadratic U/f
Voltage/frequency ratio, 5 points
Flux vector control without sensor, standard
Voltage/frequency ratio, automatic IR compensation (U/f + automatic Uo) |
torque accuracy |
+/- 15 % |
transient overtorque |
120 % of nominal motor torque +/- 10 % for 60 s |
acceleration and deceleration ramps |
Linear adjustable separately from 0.01 to 3200 s
Automatic based on the load |
motor slip compensation |
Automatic whatever the load
Adjustable
Not available in voltage/frequency ratio motor control |
switching frequency |
6...16 kHz adjustable
12...16 kHz with derating factor |
nominal switching frequency |
12 kHz |
braking to standstill |
By DC injection |
network frequency |
47.5...63 Hz |
prospective line Isc |
5 kA |
protection type |
Overheating protection: drive
Thermal power stage: drive
Short-circuit between motor phases: drive
Input phase breaks: drive
Overcurrent between output phases and earth: drive
Overvoltages on the DC bus: drive
Break on the control circuit: drive
Against exceeding limit speed: drive
Line supply overvoltage and undervoltage: drive
Line supply undervoltage: drive
Against input phase loss: drive
Thermal protection: motor
Motor phase break: motor
With PTC probes: motor |
width |
107 mm |
height |
143 mm |
depth |
150 mm |
net weight |
1.8 kg |